Trident Giant 40M – CB
Item Number: C00965
Warranty: 3+7-year extended warranty
Trident Giant 40M Commercial Heat Pump
The Trident Giant 40M is a heat pump designed for commercial use, capable of both heating and cooling, and equipped with a separate CB control unit. The unit features R290 refrigerant, a Copeland twin rotary piston compressor, and a Danfoss plate heat exchanger. Its heating capacity under A7/W35 conditions is 38.62 kW, and its cooling capacity under A35/W18 conditions is 34.21 kW. It is capable of producing heating water temperatures of up to 75 °C.
The SCOP of 4.86 specified for a water temperature of 35 °C indicates high seasonal heating efficiency. The outdoor unit’s operating range for outdoor temperatures is between −25 and +43 °C, and it also features a reduced nighttime operating mode. According to the product data sheet, the product comes with a 3+7-year extended warranty.
Key features
- A heat pump designed for commercial use.
- Heating and cooling mode.
- Separate CB control unit.
- Heating water temperature up to 75 °C.
- R290 refrigerant.
- Copeland twin rotary piston compressor.
- Danfoss plate heat exchanger.
- Reduced nighttime mode.
- 3+7-year extended warranty.
Technical data
Basic Data and Energy Efficiency
- Model: Trident Giant 40M.
- Control Unit: CB.
- Heating energy efficiency class according to the product data sheet, at 35 / 55 °C: A+++ / A+++.
- Seasonal Coefficient of Performance (SCOP) at 35 / 55 °C: 4.86 / 3.71.
- Seasonal Energy Efficiency Ratio (SEER) at 18 / 7 °C: 5.82 / 3.54.
- Rated heat output (Prated) at 35 / 55 °C: 38.6 / 38.1 kW.
- Maximum thermal output according to the data sheet, at 35 / 55 °C: 38.62 / 37.54 kW.
- Annual heating energy consumption according to the data sheet, at 35 / 55 °C: 12,166 / 15,641 kWh.
Heating Capacity
- Heating capacity for A7/W35: 38.62 kW.
- Electric power consumption for the A7/W35: 12.30 kW.
- Heating efficiency (COP) for A7/W35, according to the data sheet: 3.15.
- Heating capacity for A7/W55: 37.54 kW.
- Electric power consumption for the A7/W55: 13.95 kW.
- Heating efficiency (COP) for A7/W55: 2.69.
- Heating capacity for A2/W35: 35.51 kW.
- Electric power consumption for A2/W35: 11.05 kW.
- Heating efficiency (COP) for A2/W35: 3.21.
- Heating capacity for A2/W55: 31.21 kW.
- Electric power consumption for A2/W55: 12.80 kW.
- Heating Coefficient of Performance (COP) for A2/W55: 2.44.
- Heating capacity for model A−7/W55: 21.32 kW.
- Electric power consumption for model A−7/W55: 12.37 kW.
- Heating efficiency (COP) for model A−7/W55: 1.72.
Cooling Capacity
- Cooling capacity for the A35/W18: 34.21 kW.
- Electrical power consumption for the A35/W18: 9.14 kW.
- Cooling capacity for A35/W7: 25.14 kW.
- Electric power consumption for the A35/W7: 9.41 kW.
Cooling Circuit
- Refrigerant: R290.
- Refrigerant charge: 4.2 kg.
- Compressor: Copeland twin rotary piston.
- Compressor oil: PAG.
- Number of cooling circuits: 1.
Electrical Specifications
- Rated voltage of the outdoor unit: 400 V.
- Recommended fuse rating for the outdoor unit: 3 × B30 A.
- Rated voltage of the CB control unit: 230 V.
- Recommended fuse for the CB control unit: 1 × B10 A.
Hydraulic Data
- Heat exchanger: Danfoss plate heat exchanger.
- Water-side pipe connection: G2″, male thread.
- Minimum/maximum operating pressure: 0.8/3 bar.
Operating Range and Fan Specifications
- Operating range for external temperature: between −25 and +43 °C.
- Heating water temperature: 25–75 °C.
- Cooling water temperature: 7–20 °C.
- Number of fans: 1.
Noise level
- Sound power level according to EN 12102: 62 dB(A).
- Maximum sound power level at operating limits: 81 dB(A).
- Maximum sound power level in reduced nighttime mode: 72 dB(A).
Dimensions and weight
- Outdoor unit dimensions (width × depth × height): 1170 × 970 × 1620 mm.
- Weight of the outdoor unit: 350 kg.
- Dimensions of the CB control unit (width × depth × height): 380 × 125 × 450 mm.
- Weight of the CB control unit: 10 kg.