Trident Titan Pro 08M-HB Hydrosplit Heat Pump

The Trident Titan Pro 08M-HB is a hydrosplit heat pump designed for both heating and cooling, featuring a Trident Titan Pro 08M monoblock outdoor unit and an HB hydrobox indoor hydraulic unit. The unit uses R290 refrigerant, a Hitachi twin rotary piston compressor, and a Grundfos circulation pump. Its maximum heating capacity under A7/W35 conditions is 9.6 kW, and it can produce heating water temperatures of up to 75 °C.

The SCOP of 5.23 specified for a water temperature of 35 °C indicates high seasonal heating efficiency. The HB indoor unit features an ESBE three-way valve and 2 × 3 kW backup/supplementary heating. The unit is quiet and also offers a reduced-noise night mode; in the latter, the maximum sound power level is 42 dB(A). The data sheet also lists a free remote monitoring service and 3 years of free maintenance.

Key features

  • Hydrosplit system with a monoblock outdoor unit and an indoor hydrobox.

  • Heating and cooling mode.

  • Heating water temperature up to 75 °C.

  • R290 refrigerant.

  • Hitachi twin rotary piston compressor.

  • Grundfos circulation pump.

  • ESBE three-way valve in the indoor unit.

  • 2 × 3 kW backup/supplemental heating.

  • Quiet and reduced-noise night mode.

  • Free remote monitoring service.

  • According to the product sheet, it comes with 3 years of free maintenance and up to 10 years of comprehensive warranty coverage.

Technical data

Basic Data and Energy Efficiency

  • Full system name: Trident Titan Pro 08M-HB.

  • Outdoor unit: Trident Titan Pro 08M.

  • Indoor hydraulic unit: HB (Hydro Box).

  • Heating energy efficiency class according to the product data sheet, at 35 / 55 °C: A+++ / A+++.

  • Seasonal Coefficient of Performance (SCOP) at 35 / 55 °C: 5.23 / 3.89.

  • Seasonal Energy Efficiency Ratio (SEER) at 18 / 7 °C: 6.8 / 4.23.

  • Rated heat output (Prated) at 35 / 55 °C: 7.34 / 7.31 kW.

  • Maximum heat output at 35 / 55 °C: 9.6 / 9.2 kW.

  • Annual heating energy consumption according to the data sheet, at 35 / 55 °C: 2901 / 3881 kWh.

Heating Capacity

  • Heating capacity range for A7/W35: 2.9–9.6 kW.

  • Heating capacity range for A2/W35: 3.91–9.38 kW.

  • Heating capacity range for A−7/W35: 2.96–8.52 kW.

  • Electric power consumption for the A7/W35: 1.90 kW.

  • Heating efficiency (COP) for A7/W35: 5.05.

  • Heating capacity for A7/W55: 9.2 kW.

  • Electric power consumption for the A7/W55: 2.38 kW.

  • Heating efficiency (COP) for A7/W55: 3.87.

  • Maximum heating capacity in quiet mode, for A−7/W35: 6.48 kW.

  • Maximum heating capacity in quiet mode, for A−7/W55: 5.7 kW.

Cooling Capacity

  • Cooling capacity for the A35/W18: 9.04 kW.

  • Electric power consumption for the A35/W18: 2.46 kW.

  • Cooling capacity for the A35/W7: 7 kW.

  • Electric power consumption for the A35/W7: 2.34 kW.

  • Maximum cooling capacity in quiet mode for the A35/W18 model: 7.45 kW.

  • Maximum cooling capacity in quiet mode for the A35/W7 model: 5.68 kW.

Cooling Circuit

  • Refrigerant: R290.

  • Refrigerant charge: 0.9 kg.

  • Compressor: Hitachi twin rotary piston.

  • Compressor oil: POE.

Electrical Specifications

  • Rated voltage of the outdoor unit: 230 V.

  • Recommended fuse for the outdoor unit: 1 × B20 A.

  • Nominal voltage of the HB indoor unit: 230 V.

  • Recommended fuse for the HB indoor unit: 1 × B16 A.

  • Voltage of the backup/auxiliary heating system: 400 V.

  • Recommended fuse rating for the safety/auxiliary heater, according to the data sheet: 2 × B16 A.

  • Safety/auxiliary heating output: 2 × 3 kW.

Hydraulic Data

  • Outdoor unit water-side pipe connection: G1″, male thread.

  • Indoor unit water-side pipe connection: G1″, female thread.

  • Nominal volume flow rate: 1.37 m³/h.

  • Minimum/maximum air flow rate: 0.94 / 1.8 m³/h.

  • Internal pressure drop at nominal flow rate: 23 kPa.

  • Circulation pump: Grundfos UPM4XL K 25-90 130.

  • Manufacturer of indoor three-way valves: ESBE.

  • Minimum/maximum operating pressure: 0.8/3 bar.

Operating Range and Fan Specifications

  • Operating range for external temperature: between −25 and +43 °C.

  • Heating water temperature: 25–75 °C.

  • Cooling water temperature: 7–20 °C.

  • Number of fans: 1.

  • Fan airflow: 3,280 m³/h.

Noise level

  • Sound power level according to EN 12102: 49 dB(A).

  • Maximum sound power level at operating limits: 68 dB(A).

  • Maximum sound power level in reduced nighttime mode: 42 dB(A).

Dimensions and weight

  • Outdoor unit dimensions (width × depth × height): 1260 × 400 × 1000 mm.

  • Weight of the outdoor unit: 125 kg.

  • Dimensions of the HB indoor unit (width × depth × height): 550 × 260 × 650 mm.

  • Weight of the HB indoor unit: 33 kg.


 
Trident Titan Pro 08M – HB