Trident Titan Pro 12M – CB
Item Number: C00951
Guarantee: 10 years
Trident Titan Pro 12M-CB Monoblock Heat Pump
The Trident Titan Pro 12M-CB is a monoblock heat pump designed for both heating and cooling, featuring a Trident Titan Pro 12M outdoor unit and a CB indoor control unit. The unit features R290 refrigerant, a Hitachi twin rotary piston compressor, an Alfa Laval plate heat exchanger, and a Grundfos circulation pump. Its maximum heating capacity under A7/W35 conditions is 12.5 kW, and it can produce heating water temperatures of up to 75 °C.
The SCOP of 5.48 specified for a water temperature of 35 °C indicates high seasonal heating efficiency. The unit also features a reduced nighttime operating mode, in which the maximum sound power level is 45 dB(A). The data sheet also lists a free remote monitoring service and 3 years of free maintenance.
Key features
- Monoblock design, with a separate indoor control unit.
- Heating and cooling mode.
- Heating water temperature up to 75 °C.
- R290 refrigerant.
- Hitachi twin rotary piston compressor.
- Alfa Laval plate heat exchanger.
- Grundfos circulation pump.
- Quiet and reduced-noise night mode.
- Free remote monitoring service.
- According to the product sheet, it comes with 3 years of free maintenance and up to 10 years of comprehensive warranty coverage.
Technical data
Basic Data and Energy Efficiency
- Full system name: Trident Titan Pro 12M-CB.
- Outdoor unit: Trident Titan Pro 12M.
- Indoor control unit: CB (Control Box).
- Heating energy efficiency class according to the product data sheet, at 35 / 55 °C: A+++ / A+++.
- Seasonal Coefficient of Performance (SCOP) at 35 / 55 °C: 5.48 / 4.12.
- Seasonal Energy Efficiency Ratio (SEER) at 18 / 7 °C: 7.62 / 4.66.
- Rated heat output (Prated) at 35 / 55 °C: 9.83 / 9.6 kW.
- Annual heating energy consumption according to the data sheet, at 35 / 55 °C: 3706 / 4812 kWh.
Heating Capacity
- Heating capacity range for A7/W35: 3.55–12.5 kW.
- Heating capacity range for A2/W35: 4.89–11.78 kW.
- Heating capacity range for A−7/W35: 4.01–10.8 kW.
- Electric power consumption for the A7/W35: 2.61 kW.
- Heating efficiency (COP) for A7/W35: 4.81.
- Maximum heating capacity in quiet mode, for A−7/W35: 8.46 kW.
Cooling Capacity
- Cooling capacity for A35/W18: 12.18 kW.
- Electric power consumption for the A35/W18: 2.95 kW.
- Cooling capacity for the A35/W7: 9.21 kW.
- Electric power consumption for the A35/W7: 2.78 kW.
- Maximum cooling capacity in quiet mode for the A35/W18 model: 11.23 kW.
Cooling Circuit
- Refrigerant: R290.
- Refrigerant charge: 1.2 kg.
- Compressor: Hitachi twin rotary piston.
- Compressor oil: POE.
Electrical Specifications
- Rated voltage of the outdoor unit: 400 V.
- Recommended fuse rating for the outdoor unit: 3 × B16 A.
- Rated voltage of the indoor control unit: 230 V.
- Recommended fuse for the indoor control unit: 1 × B10 A.
Hydraulic Data
- Heat exchanger: Alfa Laval plate heat exchanger.
- Water-side pipe connection: G1″, male thread.
- Nominal volumetric flow rate: 2.05 m³/h.
- Minimum/maximum air flow rate: 1.44 / 2.7 m³/h.
- Internal pressure drop at nominal flow rate: 23 kPa.
- Circulation pump: Grundfos UPM4XL K 25-90 130.
- Minimum/maximum operating pressure: 0.8/3 bar.
Operating range
- Operating range for external temperature: between −25 and +43 °C.
- Heating water temperature: 25–75 °C.
- Cooling water temperature: 7–20 °C.
- Number of fans: 1.
- Fan airflow: 5,000 m³/h.
Noise level
- Sound power level according to EN 12102: 50 dB(A).
- Maximum sound power level at operating limits: 70 dB(A).
- Maximum sound power level in reduced nighttime mode: 45 dB(A).
Dimensions and weight
- Outdoor unit dimensions (width × depth × height): 1260 × 400 × 1000 mm.
- Outdoor unit weight: 140 kg.
- Dimensions of the indoor control unit (width × depth × height): 570 × 260 × 550 mm.
- Weight of the indoor control unit: 25 kg.