Trident Giant 30M Commercial Heat Pump
The Trident Giant 30M is a heat pump designed for commercial use, capable of both heating and cooling, and equipped with a separate CB control unit. The unit features R290 refrigerant, a Mitsubishi Electric twin rotary piston compressor, and a Danfoss plate heat exchanger. Its maximum heating capacity under A7/W35 conditions is 30.73 kW, and its maximum cooling capacity under A35/W18 conditions is 30.65 kW. It is capable of producing heating water temperatures of up to 75 °C.
The SCOP of 5.10 specified for a water temperature of 35 °C indicates high seasonal heating efficiency. The outdoor unit, equipped with two fans, has an outdoor temperature operating range of −25 to +43 °C and also features a reduced nighttime operating mode. According to the data sheet, the product comes with a 3+7-year extended warranty.
Key features
A heat pump designed for commercial use.
Heating and cooling mode.
Separate CB control unit.
Heating water temperature up to 75 °C.
R290 refrigerant.
Mitsubishi Electric twin rotary piston compressor.
Danfoss plate heat exchanger.
Outdoor unit with two fans.
Reduced nighttime mode.
3+7-year extended warranty.
Technical data
Basic Data and Energy Efficiency
Model: Trident Giant 30M.
Control Unit: CB.
Heating energy efficiency class according to the product data sheet, at 35 / 55 °C: A+++ / A+++.
Seasonal Coefficient of Performance (SCOP) at 35 / 55 °C: 5.10 / 3.83.
Seasonal Energy Efficiency Ratio (SEER) at 18 / 7 °C: 5.51 / 3.72.
Rated heat output (Prated) at 35 / 55 °C: 29.1 / 29.3 kW.
Maximum thermal output according to the data sheet, at 35 / 55 °C: 30.73 / 29.18 kW.
Annual heating energy consumption according to the data sheet, at 35 / 55 °C: 10,129 / 12,950 kWh.
Heating Capacity
Heating capacity range for A7/W35: 8.33–30.73 kW.
Heating capacity range for A2/W35: 12.14–27.51 kW.
Heating capacity range for A−7/W35: 10.07–26.28 kW.
Electric power consumption for the A7/W35: 6.95 kW.
Heating Coefficient of Performance (COP) for A7/W35: 4.42.
Heating capacity for A7/W55: 29.18 kW.
Electric power consumption for the A7/W55: 9.81 kW.
Heating Coefficient of Performance (COP) for A7/W55: 2.97.
Heating capacity for model A−7/W35: 26.28 kW.
Electric power consumption for model A−7/W35: 9.14 kW.
Heating Coefficient of Performance (COP) for A−7/W35: 2.87.
Heating capacity for model A−7/W55: 25.16 kW.
Electric power consumption for model A−7/W55: 12.10 kW.
Heating efficiency (COP) for the A−7/W55 model: 2.08.
Cooling Capacity
Cooling capacity for the A35/W18: 30.65 kW.
Electric power consumption for the A35/W18: 8.89 kW.
Cooling capacity for A35/W7: 23.45 kW.
Electric power consumption for the A35/W7: 8.93 kW.
Cooling Energy Efficiency Ratio (EER) for model A35/W7: 2.63.
Cooling Circuit
Refrigerant: R290.
Refrigerant charge: 2.7 kg.
Compressor: Mitsubishi Electric twin rotary piston.
Compressor oil: P 46M.
Number of cooling circuits: 1.
Electrical Specifications
Rated voltage of the outdoor unit: 400 V.
Recommended fuse rating for the outdoor unit: 3 × B25 A.
Rated voltage of the CB control unit: 230 V.
Recommended fuse for the CB control unit: 1 × B10 A.
Hydraulic Data
Heat exchanger: Danfoss plate heat exchanger.
Water-side pipe connection: G6/4″, male thread.
Minimum/maximum operating pressure: 0.8/3 bar.
Operating Range and Fan Specifications
Operating range for external temperature: between −25 and +43 °C.
Heating water temperature: 25–75 °C.
Cooling water temperature: 7–20 °C.
Number of fans: 2.
Noise level
Sound power level according to EN 12102: 55 dB(A).
Maximum sound power level at operating limits: 74 dB(A).
Maximum sound power level in reduced nighttime mode: 67 dB(A).
Dimensions and weight
Outdoor unit dimensions (width × depth × height): 1540 × 550 × 1740 mm.
Weight of the outdoor unit: 340 kg.
Dimensions of the CB control unit (width × depth × height): 380 × 125 × 450 mm.
Weight of the CB control unit: 10 kg.